3−90
The output logic conversion is programmable for terminal [11], [12] and the alarm relay
terminal. The open-collector output terminal [11] and [12] defaults to normally open (active
low), but you can select normally closed (active high) for the terminal in order to invert the
sense of the logic. You can invert the logical sense of the alarm relay output as well.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
C031
Output [11] active state Select logic conversion, two option
codes:
00…normally open [NO]
01…normally closed [NC]
U
00
−
C032
Output [12] active state
U
00
−
C036
Alarm relay active state
U
01
−
You can also adjust the output with ON/OFF delays.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
C130
Output [11] on delay Set range is 0.0 to 100.0 sec.
U
0.0 Sec.
C131
Output [11] off delay
U
0.0 Sec.
C132
Output [12] on delay
U
0.0 Sec.
C133
Output [12] off delay
U
0.0 Sec.
C140
Relay output on delay
U
0.0 Sec.
C141
Relay output off delay
U
0.0 Sec.
NOTE: If you are using the output terminal OFF delay feature (any of C145, C149 > 0.0
sec.), the [RS] (reset) terminal affects the ON-to-OFF transition slightly. Normally (with
using OFF delays), the [RS] input causes the motor output and the logic outputs to turn
OFF together, immediately. However, when any output uses an OFF delay, then after
the [RS] input turns ON, that output will remain ON for an additional 1 sec. period
(approximate) before turning OFF.