354
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
B031
Software lock mode
selection
Prevents parameter changes, in
five options, option codes:
00all parameters except B031
are locked when [SFT] terminal
is ON
01all parameters except B031 and
output frequency F001 are locked
when [SFT] terminal is ON
02all parameters except B031 are
locked
03all parameters except B031 and
output frequency F001 are locked
10High level access including B031
See appendix C for the accessible
parameters in this mode.
U
01
NOTE: To disable parameter editing when using B031 lock modes 00 and 01, assign the
[SFT] function to one of the intelligent input terminals.
See “Software Lock
” in chapter 4
Motor Cable Length Parameter
To achieve higher motor control performance, the WJ200 inverter has the Motor Cable
Length Parameter setting B033. Normally there is no need to adjust this parameter,
however in case of long motor cable and/or shielded cable, where there is a
comparatively higher earth capacitance, set this parameter higher to achieve better
motor control performance.
Note that the parameter is indicative and no formula to calculate the suitable value.
Normally, longer the motor cable, bigger the set value. Please adjust depending on your
system.
For 11 and 15kW inverter, it is not needed to set b033.
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
B033
Motor cable length
parameter
Set range is 5 to 20.
U
10.