441
Add Frequency Enable
The inverter can add or subtract an offset value to the output frequency setting which
is specified by A001 (will work with any of the five possible sources). The ADD
Frequency is a value you can store in parameter A145. The ADD Frequency is summed
with or subtracted from the output frequency setting only when the [ADD] terminal is
ON. Function A146 selects whether to add or subtract. By configuring an intelligent
input as the [ADD] terminal, your application can selectively apply the fixed value in
A145 to offset (positively or negatively) the inverter output frequency in real time.
Option
Code
Terminal
Symbol
Function Name State Description
50
ADD ADD Frequency
Enable
ON
Applies the A145 Add Frequency value to the output
frequency
OFF Does not apply the Add frequency. The output
frequency retains its normal value
Valid for inputs:
C001~C007
Example (default input configuration shown—see
page 3–84):
See I/O specs on page 4–6.
Required settings
A001, A145, A146
Notes:
A001 may specify any source; the Add Frequency
will be added to or subtracted from that value to
yield output frequency value.
Keypad potentiometer
Control terminal
Function F001 setting
ModBus network input
Calculate function output
Σ
+
A001
Frequency source setting
Output frequency setting
A145
A
DD frequency
A146
A
DD direction select
+/-
Intelligent input
[ADD]
ADD
7654321L
PCS
P24
PLC