355
Run/power ON warning time
Inverter outputs the operation time over (RNT) or the plug-in time over (ONT) signal
when the time specified as the run/power ON warning time (b034) is exceeded.
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
b034
Run/power ON warning
time
Range is,
0.:Warning disabled
1. to 9999.:
10~99,990 hrs (unit: 10)
1000 to 6553:
100,000~655,350 hrs (unit: 100)
U
0.
Hrs.
(1) Operation time over (RNT) signal
To use this signal function, assign function “11 (RNT)” to one of the intelligent
output terminals [11] to [12] (C021 to C022), or to the alarm relay output (C026).
Specify the run/power-ON warning time (b034).
(2) Plug-in time over (ONT) signal
To use this signal function, assign function “12 (ONT)” to one of the intelligent
output terminals [11] to [12] (C021 to C022), or to the alarm relay output (C026).
Specify the run/power-ON warning time (b034).
Rotation restriction related parameters
Rotation direction restriction: b035 The rotation direction restriction function allows
you to restrict the direction of the motor rotation. This function is effective regardless of
the specification of operation command input device (e.g., control terminal or integrated
operator). If an operation command to drive the motor in a restricted direction is given,
the inverter (display) shows ( ).
Reverse run protection: b046 The reverse run protection function is effective when
03 (sensorless vector control)” or “04 (0-SLV)” is specified for the V/F characteristic
selection (A044). For control reasons, especially during motor operation at low speed, the
inverter may output a frequency that instructs the motor to rotate in the direction
opposite to that specified by the operation command.
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
B035
Rotation direction
restriction
Three option codes:
00No restriction
01Reverse rotation is restricted
02Forward rotation is restricted
U
00
b046
Reverse run protection Two option codes:
00No protection
01Reverse rotation is protected
U
00