B−3
Connecting the Inverter to ModBus
Modbus connector is in control terminal block as below. Note that RJ45 connector
(RS-422) is used for external operator only.
Terminate Network Wiring - The RS-485 wiring must be terminated at each physical
end to suppress electrical reflections and help decrease transmission errors. WJ200 has
a built-in 200
Ω resistor activated by a dip switch. Select termination resistors that match
the characteristic impedance of the network cable. The diagram above shows a network
with the needed termination resistor at each end.
PLC