3−42
Add Frequency – The inverter can add or subtract on offset value to the output
frequency setting which is specified by A001 (will work with any of the five possible
sources). The ADD Frequency is a value you can store in parameter A145. the ADD
Frequency is summed with or subtracted from the output frequency setting only when
the [ADD] terminal is ON. Function A146 selects whether to add or subtract. By
configuring an intelligent input as the [ADD] terminal, your application can selectively
apply the fixed value in A145 to offset (positively or negatively) the inverter output
frequency in real time.
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
A145
ADD frequency An offset value that is applied
to the output frequency when
the [ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
Two options:
00…Plus (adds A145 value to
the output frequency
setting)
01…Minus (subtracts A145
value from the output
frequency setting)
0.00 Hz
A146
ADD direction select
U
00
−
Keypad potentiometer
Control terminal
Function F001 setting
ModBus network input
Calculate function output
Σ
+
A001
Frequency source setting
Output frequency setting
A145