4−67
Zero Hz Speed Detection Signal
The inverter outputs the 0Hz speed detection signal when the inverter output
frequency falls below the threshold level (C063).
To use this function, assign “21 (ZS)” to one of the intelligent output terminals.
Option
Code
Terminal
Symbol
Function Name State Description
21
ZS Zero Hz speed
detection signal
ON
Output frequency is less than C063
OFF
Output frequency is not less than C063
alid for inputs:
11, 12, AL0 – AL2 Example for terminal [11] (default output
configuration shown – see page 3-90):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see page 4-52 and 3-90):
See I/O specs on page 4-6
Required settings
C063
Notes:
• The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative-going turn-off spike generated by the coil
from damaging the inverter’s output transistor.
RY
Inverter output
terminal circuit
CM2 11
ZS
AL1
Power
supply
Load
AL0 AL2
Inverter logic
circuit board
ZS