EasyManua.ls Logo

Hitachi WJ200 Series

Hitachi WJ200 Series
420 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
487
Analog Input Operation
The WJ200 inverters provide for analog input
to command the inverter frequency output
value. The analog input terminal group
includes the [L], [OI], [O], and [H] terminals on
the control connector, which provide for Voltage
[O] or Current [OI] input. All analog input
signals must use the analog ground [L].
If you use either the voltage or current analog
input, you must select one of them using the
logic input terminal function [AT] analog type.
Refer to the table on next page showing the
activation of each analog input by combination
of A005 set parameter and [AT] terminal
condition. The [AT] terminal function is covered
in “Analog Input Current/Voltage Select” in
section 4. Remember that you must also set
A001 = 01 to select analog input as the
frequency source.
NOTE: If no logic input terminal is configured for the [AT] function, then inverter
recognizes that [AT]=OFF and MCU recognizes [O]+[OI] as analog input.
Using an external potentiometer is a common way
to control the inverter output frequency (and a good
way to learn how to use the analog inputs). The
potentiometer uses the built-in 10V reference [H]
and the analog ground [L] for excitation, and the
voltage input [O] for the signal. By default, the [AT]
terminal selects the voltage input when it is OFF.
Take care to use the proper resistance for the
potentiometer, which is 1~2 k
Ω, 2 Watts.
Voltage Input The voltage input circuit uses
terminals [L] and [O]. Attach the signal cable’s
shield wire only to terminal [L] on the inverter.
Maintain the voltage within specifications (do
not apply negative voltage).
Current Input The current input circuit uses
terminals [OI] and [L]. The current comes from a
sourcing
type transmitter; a
sinking
type will not
work! This means the current must flow into
terminal [OI], and terminal [L] is the return back
to the transmitter. The input impedance from
[OI] to [L] is 100 Ohms. Attach the cable shield
wire only to terminal [L] on the inverter.
AM H O OI L
+V Ref.
Voltage input
Current input
A
GND
AM H O OI L
Freq.
settin
g
A001
V/I input
select
[AT]
Å
+
-
4-20 mA
0-10 V
AM H O OI L
1 to 2kΩ, 2W
0 to 9.6 VDC,
0 to 10V nominal
AM H O OI L
+
-
4 to 19.6 mA DC,
4 to 20mA nominal
AM H O OI L
Å
See I/O specs on page 4-6.

Table of Contents

Other manuals for Hitachi WJ200 Series

Related product manuals