234
Monitoring Parameters with the Display
After using the keypad for parameter editing, it’s a
good idea to switch the inverter from Program Mode
to Monitor Mode. The PRG LED will be OFF, and the
Hertz or Ampere LED indicates the display units.
For the powerup test, monitor the motor speed
indirectly by viewing the inverters output frequency.
The output frequency must not be confused with base
frequency (50/60 Hz) of the motor, or the carrier
frequency (switching frequency of the inverter, in the
kHz range). The monitoring functions are in the “D”
list, located near the top left of the “Keypad
Navigation Map”on page 2-26.
Output frequency (speed) set – Resuming keypad operation from the previous table,
follow the steps below.
Action Display Func./Parameter
(Starting point)
H004
Motor poles parameter
Press the ESC key four times
F001
F001 is selected
Press the SET key.
b100
Set frequency displayed
Running the Motor
If you have programmed all the parameters up to this point, you’re ready to run the
motor! First, review this checklist:
1. Verify the power LED is ON. If not, check the power connections.
2. Verify the Run Key Enable LED is ON. If it is OFF, check the A002 setting.
3. Verify the PRG LED is OFF. If it is ON, review the instructions above.
4. Make sure the motor is disconnected from any mechanical load.
5. Now, press the RUN key on the keypad. The RUN LED will turn ON.
6. Press the [U] key for a few seconds. The motor should start turning.
7. Press the STOP key to stop the motor rotation.
1
2
RUN
ESC
STOP/
RESET
SET
8888
RUN PWR
Hz ALM
A
PRG
d.0.0.1.