PID deviation output – If PID deviation "ε" exceeds the value in C044, output signal
configured as 04 (OD) is activated.
PID feedback comparison output – If PID feedback is out of the range between C052
and C053 output signal configured as 31 (FBV) is activated.
PID scaling – When PID scale parameter (A075) is set, following variables are scaled.
(monitored) = (variable) ×(A075
d004 F001 A011 A012 A020 A220 A021 A022
A023 A024 A025 A026 A027 A028 A029 A030
A031 A032 A033 A034 A035 A101 A102 A145
PID Sleep Function
The inverter shuts off the output when the PID output becomes less than the specified
value (A156) in case of PID is set enabled, or shuts off when the frequency command
becomes less than the specified value in case of PID is set disabled. And if the PID
output or frequency command exceeds the specified value (A156) for a specified period
(A157), inverter automatically restarts the operation. This is the PID sleep function.
PID Sleep function is always enabled, even the PID function is disabled.
PID output
PID sleep function
triggering level A156
A157 A156
Run command (internal)
Run Stop Run
Run command (external)
Run
PID sleep function action delay time
PID feedback
C052 PID FBV output high limit
C053 PID FBV output low limit
Time
FW input
FBV output
ON
ON ON