3−99
Analog Input Signal Calibration Settings
The functions in the following table
configure the signals for the analog input
terminals. Note that these settings do not
change the current/voltage or sink/source
characteristics – only the zero and span
(scaling) of the signals.
These parameters are already adjusted
before the shipment, and therefore it is
not recommended to do the adjustment at
the customer.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
C081
O input span calibration Scale factor between the external
frequency command on terminals
L–O (voltage input) and the
frequency output,
range is 0.0 to 200%
100.0 %
C082
OI input span calibration Scale factor between the external
frequency command on terminals
L–OI (voltage input) and the
frequency output,
range is 0.0 to 200%
100.0 %
C085
Thermistor input (PTC)
span calibration
Scale factor of PTC input.
Range is 0.0 to 200%
100.0 %
NOTE: When you restore factory default settings, the values will change to those listed
above. Be sure to manually reconfigure the values for your application, if needed, after
restoring factory defaults.
Max. freq
Max. freq /2
10V, 20mA 5V, 12mA
200%
100%
50%
0
0V, 4mA
Freq setpoint