3−40
For use of EL-S curve be sure to use select frequency source as multi-speed, to avoid nuisance
change of frequency during acceleration and deceleration.
Additional Analog Input Settings
Input Range Settings – The parameters in the following table adjust the input
characteristics of the analog current input. When using the inputs to command the
inverter output frequency, these parameters adjust the starting and ending ranges for
the current, as well as the output frequency range. Related characteristic diagrams are
located in “
Analog Input Settings” on page 3-16.
Analog sampling setting is the value specified in A016.
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
A101
[OI] input active range start
frequency
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
U
0.00 Hz
A102
[OI] input active range end
frequency
U
0.0 Hz
A103
[OI] input active range start
current
The starting point (offset) for
the current input range,
range is 0. to 100.%
The ending point (offset) for
the current input range,
range is 0. to 100.%
U
20. %
A104
[OI] input active range end
current
U
100. %
A105
[OI] input start frequency
select
Two options; select codes:
00…Use offset (A101 value)
01…Use 0Hz
U
00
−
Refer to parameter A011 to A015 for analog voltage input.