485
2
nd
Motor Selection
This function allows you to switch the inverter setting to control two different types of
motors. To use this function, assign function “08” to one of the input terminal and make
it on or off. When 2
nd
motor parameters are selected, output signal SETM turns on.
No. Codes Description No. Codes Description
1
F202
Acceleration time (1) 22
A295
Acc1 to Acc2 frequency transition point
2
F203
Deceleration time (1) 23
A296
Dec1 to Dec2 frequency transition point
3
A201
Frequency source 24
C241
Overload warning level
4
A202
Run command source 25
H202
Motor data selection
5
A203
Base frequency 26
H203
Motor capacity
6
A204
Maximum frequency 27
H204
Motor poles
7
A220
Multi-speed frequency 0 28
H205
Motor speed response
8
A241
Torque boost select 29
H206
Motor stabilization constant
9
A242
Manual torque boost value 30
H220
Motor constant R1 (Hitachi motor)
10
A243
Manual torque boost freq. 31
H221
Motor constant R2 (Hitachi motor)
11
A244
V/f characteristic curve 32
H222
Motor constant L (Hitachi motor)
12
A245
V/f gain 33
H223
Motor constant I0 (Hitachi motor)
13
A246
Voltage comp. gain for automatic torque boost 34
H224
Motor constant J (Hitachi motor)
14
A247
Slip comp. gain for automatic torque boost 35
H230
Motor constant R1 (Auto tuned data)
15
A261
Frequency upper limit 36
H231
Motor constant R2 (Hitachi motor)
16
A262
Frequency lower limit 37
H232
Motor constant L (Hitachi motor)
17
A281
AVR function select 38
H233
Motor constant I0 (Hitachi motor)
18
A282
AVR voltage select 39
H234
Motor constant J (Hitachi motor)
19
A292
Acceleration time (2)
20
A293
Deceleration time (2)
21
A294
Select method to switch to Acc2/Dec2 profile
Option
Code
Terminal
Symbol
Function Name State Description
60
SETM 2
nd
motor selection
ON 2
n
d
motor parameter sets are selected
OFF 1
s
t
motor parameter sets are selected
V
alid for inputs:
11, 12, AL0 – AL2 Example for terminal [11] (default output
configuration shown – see page 3-90):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see page 4-52 and 3-90):
See I/O specs on page 4-6
Required settings
Notes:
RY
Inverter output
terminal circuit
CM2 11
SETM
AL1
Power
supply
Load
AL0 AL2
Inverter logic
circuit board
SETM