6−14
Restoring Factory Default Settings
You can restore all inverter parameters to the original factory (default) settings
according to area of use. After initializing the inverter, use the powerup test in Chapter
2 to get the motor running again. If operation mode (std. or high frequency) mode is
changed, inverter must be initialized to activate new mode. To initialize the inverter,
follow the steps below.
(1) Select initialization mode in b084.
(2) If b084=02, 03 or 04, select initialization target data in b094.
(3) If b084=02, 03 or 04, select country code in b085.
(4) Set 01 in b180.
(5) The following display appears for a few seconds, and initialization is completed with
d001 displayed.
Display during initialization
Initialization of trip history
5 HC
Initialization
mode
Initialization for area A
5 00
Initialization for area B
5 01
The left digit rotates during initialization
d001
Blinking alternately
HD mode
Operation
mode after
initialization
ND mode
“B” Function
Func.
Code
Name Description
B084
Initialization mode
(parameters or trip
history)
Select initialized data, five option codes:
00…Initialization disabled
01…Clears Trip history
02…Initializes all Parameters
03…Clears Trip history and initializes all parameters
04…Clears Trip history and initializes all parameters and EzSQ
program
b094
Initialization target
data setting
Select initialized parameters, four option codes:
00…All parameters
01…All parameters except in/output terminals and communication.
02…Only registered parameters in Uxxx.
03…All parameters except registered parameters in Uxxx and b037.
B085
Initial value select Select default parameter values:
00…area A 01…area B
b180
Initialization trigger
This is to perform initialization by parameter input with b084, b085
and b094. Two option codes:
00…Initialization disable
01…Perform initialization
Data of b084 is not saved in EEPROM to avoid unintentional initializing.