3−102
Output Logic and Timing
Logic Output Function – The inverter has a built-in logic output feature. Select any two
operands out of all intelligent output options except LOG1~LOG3 and their operator out
of AND, OR, or XOR (exclusive OR). The terminal symbol for the new output is [LOG].
Use C021, C022 or C026 to route the logical result to terminal [11], [12] or the relay
terminals. LOG1-LOG3, no, OPO cannot be the operand.
The following table shows all four possible input combinations with each of the three
available logic operations.
Operand Operator
A B AND OR XOR
0 0 0 0 0
0 1 0 1 1
1 0 0 1 1
1 1 1 1 0
Intelligent outputs
used as internal
inputs:
RUN, FA1, FA2,
OL, OD, AL, Dc,
…EDM
Operand A
C142/C145