3−94
Low Load Detection Parameters
The following parameters work in
conjunction with the intelligent output
function, when configured. The output
mode parameter (C038) sets the mode of
the detection at which the low load
detection signal [LOC] turns ON. Three
kinds of modes can be selected. The
detection level parameter (C039) is to set
the level of the low load.
This function is for generating an early
warning logic output, without causing
either a trip event or a restriction of the
motor current (those effects are available
on other functions).
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
C038
Output mode of low
current detection
Two option codes:
00…During acceleration,
deceleration and constant speed
01…During constant speed only
U
01
−
C039
Low current detection
level
Set the level of low load detection,
range is 0.0 to 2.0*inverter rated
current
U
INV rated
current
A
C039