398
Network Communications Settings
The following table lists parameters that configure the inverters serial communications
port. The settings affect how the inverter communication with a digital operator (such
as SRW-0EX), as well as a ModBus network (for networked inverter applications). The
settings cannot be edited via the network, in order to ensure network reliability. Refer to
“ModBus Network Communications” on page B-1 for more information on controlling
any monitoring your inverter from a network.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
C071
Communication speed Eight option codes:
032,400 bps
044,800 bps
059,600 bps
0619,200 bps
0738,400 bps
0857,600 bps
0976,800 bps
10115,200 bps
U
05 baud
C072
Modbus address Set the address of the inverter on
the network. Range is 1 to 247
U
1.
C074
Communication parity Three option codes:
00No parity
01Even parity
02Odd parity
U
00
C075
Communication stop bit Two option codes:
11 bit
22 bit
U
1 bit
C076
Communication error
select
Selects inverter response to
communications error.
Five options:
00Trip
01Decelerate to a stop and trip
02Disable
03Free run stop (coasting)
04Decelerates to a stop
U
02
C077
Communication error
time-out
Sets the communications
watchdog timer period.
Range is 0.00 to 99.99 sec
0.0 = disabled
U
0.00 sec.
C078
Communication wait
time
Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms
U
0. msec.
C071
Communication speed Eight option codes:
032,400 bps
044,800 bps
059,600 bps
0619,200 bps
0738,400 bps
0857,600 bps
0976,800 bps
10115,200 bps
U
05 baud