Network Communications Settings
The following table lists parameters that configure the inverter’s serial communications
port. The settings affect how the inverter communication with a digital operator (such
as SRW-0EX), as well as a ModBus network (for networked inverter applications). The
settings cannot be edited via the network, in order to ensure network reliability. Refer to
“ModBus Network Communications” on page B-1 for more information on controlling
any monitoring your inverter from a network.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
C071
Communication speed Eight option codes:
03…2,400 bps
04…4,800 bps
05…9,600 bps
06…19,200 bps
07…38,400 bps
08…57,600 bps
09…76,800 bps
10…115,200 bps
U
05 baud
C072
Modbus address Set the address of the inverter on
the network. Range is 1 to 247
U
1.
−
C074
Communication parity Three option codes:
00…No parity
01…Even parity
02…Odd parity
U
00
−
C075
Communication stop bit Two option codes:
1…1 bit
2…2 bit
U
1 bit
C076
Communication error
select
Selects inverter response to
communications error.
Five options:
00…Trip
01…Decelerate to a stop and trip
02…Disable
03…Free run stop (coasting)
04…Decelerates to a stop
U
02
−
C077
Communication error
time-out
Sets the communications
watchdog timer period.
Range is 0.00 to 99.99 sec
0.0 = disabled
U
0.00 sec.
C078
Communication wait
time
Time the inverter waits after
receiving a message before it
transmits.
Range is 0. to 1000. ms
U
0. msec.