3−97
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
C053
PID FBV output
low limit
When the PV goes below this
value, the PID loop turns ON the
PID second stage output, range is
0.0 to 100%
U
0.0 %
C054
Over-torque/under-torque
selection
Two option codes:
00…Over-torque
01…Under-torque
U
00
−
C055
Over/under-torque level
(Forward powering mode)
Set range is 0 to 200%
U
100. %
C056
Over/under-torque level
(Reverse regen. mode)
Set range is 0 to 200%
U
100. %
C057
Over/under-torque level
(Reverse powering mode)
Set range is 0 to 200%
U
100. %
C058
Over/under-torque level
(Forward regen. mode)
Set range is 0 to 200%
U
100. %
C059
Signal output mode of
Over/under-torque
Two option codes:
00…During accel.,
decel. and constant
speed
01…During constant speed only
U
01
−
C061
Electronic thermal
warning level
Set range is 0 to 100%
Setting 0 means disabled.
U
90 %
C063
Zero speed detection level Set range is 0.0 to 100.0Hz
U
0.00 Hz
C064
Heat sink overheat
warning
Set range is 0 to 110 °C
U
100.
°C
C111
Overload warning level 2 Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Rated current
x 1.15
A