3−9
“d” Function
Run
Mode
Edit
Units
Func.
Code
Name Description
D102
DC bus voltage monitor Voltage of inverter internal DC bus,
Range is 0.0 to 999.9
−
V
d103
BRD load ratio monitor Usage ratio of integrated brake
chopper, range is 0.0~100.0%
−
%
D104
Electronic thermal monitor Accumulated value of electronic
thermal detection, range is from
0.0~100.0%
−
%
Trip Event and History Monitoring
The trip event and history monitoring feature lets you cycle through related information
using the keypad. See “Monitoring Trip Events, History, & Conditions
” on page 6-5 for
more details.
“d” Function
Run
Mode
Edit
Units
Func.
Code
Name Description
D080
Trip counter Number of trip events,
Range is 0. to 65530
−
events
D081
Trip monitor 1 Displays trip event information:
• Error code
• Output frequency at trip point
• Motor current at trip point
• DC bus voltage at trip point
• Cumulative inverter operation
time at trip point
• Cumulative power-ON time at
trip point
− −
D082
Trip monitor 2
− −
D083
Trip monitor 3
− −
d084
Trip monitor 4
− −
d085
Trip monitor 5
− −
d086
Trip monitor 6
− −
d090
Warning monitor Displays the warning code
− −