Analog Input Calculate Function – The inverter can mathematically combine two input
sources into one value. The Calculate function can either add, subtract, or multiply the
two selected sources. This provides the flexibility needed by various applications. You
can use the result for the output frequency setting (use A001=10) or for the PID Process
Variable (PV) input (use A075=03).
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
A141
A input select for calculate
function
Seven options:
00Operator
01VR
02Terminal [O] input
03Terminal [OI] input
04RS485
05Option
07Pulse train input
Seven options:
00Operator
01VR
02Terminal [O] input
03Terminal [OI] input
04RS485
05Option
07Pulse train input
U
02
A142
B input select for calculate
function
U
03
A143
Calculation symbol Calculates a value based on
the A input source (A141
selects) and B input source
(A142 selects).
Three options:
00ADD (A input + B input)
01SUB (A input - B input)
02MUL (A input * B input)
U
00
Digital operator
Potentiometer
[O] input
[OI] input
Network variable
A141
A
input select
A142
B in41ut select
A + B
A - B
A * B
A
B
A143
Digital operator
Potentiometer
[O] input
[OI] input
Network variable
“CAL”
(result)