3−89
Output Terminal Configuration
The inverter provides configuration for logic (discrete) and analog outputs, shown in the
table below.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
C021
Output [11] function
[EDM assignable]
48 programmable functions
available for logic (discrete)
outputs
(see next section)
48 programmable functions available
for logic (discrete) outputs
(see next section)
13 programmable functions:
00…Output frequency (PWM)
01…Output current (PWM)
02…Output torque (PWM)
03…Output frequency (Pulse
train)
04…Output voltage (PWM)
05…Input power (PWM)
06…Electronic thermal load ratio
(PWM)
07…LAD frequency (PWM)
08…Output current (Pulse train)
10…Heat sink temperature
(PWM)
12…General output (PWM)
15…Pulse train input monitor
16…Option(PWM)
11 programmable functions:
00…Output frequency
01…Output current
02…Output torque
04…Output voltage
05…Input power
06…Electronic thermal load ratio
07…LAD frequency
10…Heat sink temperature
11…Output torque (with code)
13…General output
16…Option
Current with digital current
monitor output at 1,440Hz
Range is 20%~200% of rated
current
Select logic conversion, two option
codes:
00…normally open [NO]
01…normally closed [NC]
U
01
[FA1]
−
C022
Output [12] function
U
00
[RUN]
−
C026
Alarm relay function
U
05
[AL]
−
C027
[EO] terminal selection
(Pulse/PWM output)
U
07
−
C028
[AM] terminal selection
(Analog voltage output
0...10V)
U
07
[LAD]
−
C030
Digital current monitor
reference value
Rated current A
C047
Pulse train input/output
scale conversion
If EO terminal is configured as
pulse train input (C027=15), scale
conversion is set in C047.
Pulse-out = Pulse-in × (C047)
Set range is 0.01 to 99.99
1.00
−