Output Terminal Configuration
The inverter provides configuration for logic (discrete) and analog outputs, shown in the
table below.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
C021
Output [11] function
[EDM assignable]
48 programmable functions
available for logic (discrete)
outputs
(see next section)
48 programmable functions available
for logic (discrete) outputs
(see next section)
13 programmable functions:
00Output frequency (PWM)
01Output current (PWM)
02Output torque (PWM)
03Output frequency (Pulse
train)
04Output voltage (PWM)
05Input power (PWM)
06Electronic thermal load ratio
(PWM)
07LAD frequency (PWM)
08Output current (Pulse train)
10Heat sink temperature
(PWM)
12General output (PWM)
15Pulse train input monitor
16Option(PWM)
11 programmable functions:
00Output frequency
01Output current
02Output torque
04Output voltage
05Input power
06Electronic thermal load ratio
07LAD frequency
10Heat sink temperature
11Output torque (with code)
13General output
16Option
Current with digital current
monitor output at 1,440Hz
Range is 20%~200% of rated
current
Select logic conversion, two option
codes:
00normally open [NO]
01normally closed [NC]
U
01
[FA1]
C022
Output [12] function
U
00
[RUN]
C026
Alarm relay function
U
05
[AL]
C027
[EO] terminal selection
(Pulse/PWM output)
U
07
C028
[AM] terminal selection
(Analog voltage output
0...10V)
U
07
[LAD]
C030
Digital current monitor
reference value
Rated current A
C047
Pulse train input/output
scale conversion
If EO terminal is configured as
pulse train input (C027=15), scale
conversion is set in C047.
Pulse-out = Pulse-in × (C047)
Set range is 0.01 to 99.99
1.00