B30
(iii) List of registers (monitoring)
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1001h
Output frequency monitor
d001 (high)
R 0 to 40000(100000) 0.01 [Hz]
1002h d001 (low)
1003h Output current monitor d002 R 0 to 65530 0.1 [A]
1004h Rotation direction minitoring d003 R
0: Stopping, 1: Forward rotation, 2:
Reverse rotation
0.1 [Hz]
1005h
Process variable (PV), PID
feedback monitoring
d004 (high)
R 0 to 1000000 0.1
1006h d004 (low)
1007h Intelligent input terminal status d005 R 2^0: Terminal 1 to 2^6: Terminal 7 1 bit
1008h Intelligent output terminal status d006 R
2^0: Terminal 11 to 2^1: Terminal 12/
2^2: Relay Terminal
1 bit
1009h
Scaled output frequency monitor
d007 (high)
R 0 to 4000000(10000000) 0.01
100Ah d007 (low)
100Bh
Actual-frequency monitor
d008 (high) R
-100000 to +100000 0.01 [Hz]
100Ch d008 (low) R
100Dh Torque command monitor d009 R -200 to +200 1 [%]
100Eh Torque bias monitor d010 R -200 to +200 1 [%]
100Fh (Reserved) - - - -
1010h Torque monitor d012 R -200 to +200 1 [%]
1011h Output voltage monitor d013 R 0 to 6000 0.1 [V]
1012h Power monitor d014 R 0 to 1000 0.1 [kW]
1013h
Watt-hour monitor
d015 (high)
R 0 to 9999000 0.1
1014h d015 (low)
1015h
Elapsed RUN time monitor
d016 (high)
R 0 to 999900 1 [h]
1016h d016 (low)
1017h
Elapsed power-on time monitor
d017 (high)
R 0 to 999900 1 [h]
1018h d017 (low)
1019h Heat sink temperature monitor d018 R -200 to 1500 0.1 []
101Ah to
(Reserved) - - - -
101Ch
101Dh Life-check monitor d022 R
2^0: Capacitor on main circuit board
2^1: cooling-fan
1 bit
101Eh
EzSQ program counter
d023
R
01024
101Fh
EzSQ program number
d024
R
09999
1020h
1025h
(Reserved) - - - -
1026h
DC voltage monitoring
(across P and N)
d102 R 0 to 10000 0.1 [V]
1027h BRD load factor monitoring d103 R 0 to 1000 0.1 [%]
1028h
Electronic thermal overload
monitoring
d104 R 0 to 1000 0.1 [%]
1029h to
102Dh
(Reserved) - - - -
102Eh
User monitor 1
d025(HIGH) R
-2147483647 to 2147483647 1
102Fh d025(LOW) R
1030h
User monitor 2
d026(HIGH) R
-2147483647 to 2147483647 1
1031h d026(LOW) R
1032h
User monitor 3
d027(HIGH) R
-2147483647 to 2147483647 1
1033h d027(LOW) R
1034h to
1035h
(Reserved) - - - -
1036h
Position setting monitor
d029(HIGH) R
-268435455 to 268435455 1
1037h d029(LOW) R
1038h
Position feedback monitor
d030(HIGH) R
-268435455 to 268435455 1
1039h d030(LOW) R
103Ah to
1056h
(reserved) - - - -
1057h Inverter mode monitor d060 R
0(IM CT)
1(IM VT)
2(IM High Freq
mode)
1058h to
1102h
unused - - Inaccessible -