EasyManua.ls Logo

Hitachi WJ200 Series

Hitachi WJ200 Series
420 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B4
Inverter Parameter Setup - The inverter has several settings related to ModBus
communications. The table below lists them together. The
Required
column indicates
which parameters
must
be set properly to allow communications. You may need to
refer to the host computer documentation in order to match some of its settings.
Func.
Code
Name Required Settings
A001 Frequency source
00
Keypad potentiometer
01Control terminal
02Function F001 setting
03ModBus network input
10 Calculate function output
A002 Run command source
01
Control terminal
02Run key on keypad, or digital operator
03 ModBus network input
C071 Communication speed
03 2400 bps
044800 bps
05 9600 bps
06 19.2k bps
0738.4k bps
0857.6k bps
0976.8k bps
10 115.2k bps
C072 Modbus Address
Network address, range is 1 to 247
C074 Communication parity
00
No parity
01Even parity
02Odd parity
C075 Communication stop bit
Range is 1 or 2
C076 Communication error select
00
Trip (Error code E60)
01Decelerate to a stop and trip
02Disable
03Free run stop (coasting)
04Decelerate to a stop
C077 Communication error time-out
Comm. Watchdog timer period,
range is 0.00 to 99.99 sec.
C078 Communication wait time
Time the inverter waits after receiving a
message before it transmits.
Range is 0. to 1000. ms
NOTE: When you change any of the parameters above, the inverter power must be
rebooted in order to activate new parameters. Instead of rebooting, turning ON/OFF of
reset terminal works as same.

Table of Contents

Other manuals for Hitachi WJ200 Series

Related product manuals