4−63
Torque Limited Signal
The inverter outputs the torque limited signal when it is in torque limit operation.
To enable this function, assign “10 (TRQ)” to an intelligent output terminal.
Refer to section 3 for detailed explanation.
Option
Code
Terminal
Symbol
Function Name State Description
10
TRQ Torque limited
signal
ON Inverter is in torque limiting mode
OFF Inverter is not in torque limiting mode
alid for inputs:
11, 12, AL0 – AL2 Example for terminal [11] (default output
configuration shown – see page 3-90):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see page 4-52 and 3-90):
See I/O specs on page 4-6
Required settings
A044=03, b040~b044
Notes:
• The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative-going turn-off spike generated by the coil
from damaging the inverter’s output transistor.
RY
Inverter output
terminal circuit
CM2 11
TRQ
AL1
Power
supply
Load
AL0 AL2
Inverter logic
circuit board
TRQ