B31
(iv) List of registers
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1103h
Acceleration time (1)
F002 (high)
R/W 1 to 360000 0.01 [sec.]
1104h F002 (low)
1105h
Deceleration time (1)
F003 (high)
R/W 1 to 360000 0.01 [sec.]
1106h F003 (low)
1107h Keypad Run key routing F004 R/W 0 (forward rotation), 1 (reverse rotation) -
1108h to
1200h
Unused - - Inaccessible -
(v) List of registers (function modes)
Parameter group A
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1201h Frequency source A001 R/W
0 (keypad potentiometer), 1 (control circuit
terminal block), 2 (digital operator), 3
(Modbus), 4 (option ), 6 (pulse train input), 7
(easy sequence), 10 (operation function result)
-
1202h Run command source (*) A002 R/W
1 (control circuit terminal block), 2 (digital
operator), 3 (Modbus), 4 (option)
-
1203h Base frequency A003 R/W 300 to "maximum frequency" 0.1 [Hz]
1204h Maximum frequency A004 R/W 300 to 4000(10000) 0.1 [Hz]
1205h [AT] selection A005 R/W
0 (switching between O and OI terminals),
2 (switching between O terminal and keypad
potentiometer),
3 (switching between OI terminal and keypad
potentiometer)
-
1206h to
120Ah
(Reserved) - - - -
120Bh
[O] input active range
start frequency
A011 (high)
R/W 0 to 40000(100000) 0.01 [Hz]
120Ch A011 (low)
120Dh
[O] input active range end
frequency
A012 (high)
R/W 0 to 40000(100000) 0.01 [Hz]
120Eh A012 (low)
120Fh
[O] input active range
start voltage
A013 R/W 0 to "[O]-[L] input active range end voltage" 1 [%]
1210h
[O] input active range end
voltage
A014 R/W "[O]-[L] input active range start voltage" to 100 1 [%]
1211h
[O] input start frequency
select
A015 R/W 0 (external start frequency), 1 (0 Hz) -
1212h Analog input filter. A016 R/W
1 to 30 or 31 (500 ms filter ±0.1 Hz with
hysteresis)
1
1213h EzSQ selection A017 R/W 0 (disabling), 1 (PRG terminal) , 2 (Always) -
1214h (Reserved) - - - -
1215h
Multi speed operation
selection
A019 R/W 0 (binary), 1 (bit) -
1216h
Multi-speed freq. 0
A020 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1217h A020 (low) R/W
1218h
Multi-speed freq. 1
A021 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1219h A021 (low) R/W
121Ah
Multi-speed freq. 2
A022 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
121Bh A022 (low) R/W
121Ch
Multi-speed freq. 3
A023 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
121Dh A023 (low) R/W
121Eh
Multi-speed freq. 4
A024 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
121Fh A024 (low) R/W
1220h
Multi-speed freq. 5
A025 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1221h A025 (low) R/W
1222h
Multi-speed freq. 6
A026 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1223h A026 (low) R/W
1224h
Multi-speed freq. 7
A027 (high) R/W
0 or "start frequency" to "maximum frequency" 0.01 [Hz]
1225h A027 (low) R/W
After changing the setting, keep the time 40ms or longer before actually give run command