B32
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
1226h
Multi-speed freq. 8
A028 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1227h A028 (low) R/W
1228h
Multi-speed freq. 9
A029 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1229h A029 (low) R/W
122Ah
Multi-speed freq. 10
A030 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
122Bh A030 (low) R/W
122Ch
Multi-speed freq. 11
A031 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
122Dh A031 (low) R/W
122Eh
Multi-speed freq. 12
A032 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
122Fh A032 (low) R/W
1230h
Multi-speed freq. 13
A033 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1231h A033 (low) R/W
1232h
Multi-speed freq. 14
A034 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1233h A034 (low) R/W
1234h
Multi-speed freq. 15
A035 (high) R/W
0 or "start frequency" to "maximum
frequency"
0.01 [Hz]
1235h A035 (low) R/W
1236h (Reserved) - - - -
1237h (Reserved) - - - -
1238h Jog frequency A038 R/W 0.0, "Start frequency" to 999(10000) 0.01 [Hz]
1239h Jog stop mode A039 R/W
0 (free-running after jogging stops [disabled
during operation])
1 (deceleration and stop after jogging stops
[disabled during operation])
2 (DC braking after jogging stops [disabled
during operation])
3 (free-running after jogging stops [enabled
during operation])
4 (deceleration and stop after jogging stops
[enabled during operation])
5 (DC braking after jogging stops [enabled
during operation])
-
123Ah (Reserved) - - - -
123Bh
Torque boost method
selection
A041 R/W
0 (manual torque boost), 1 (automatic torque
boost)
-
123Ch Manual torque boost value A042 R/W 0 to 200 0.1 [%]
123Dh
Manual torque boost
frequency
A043 R/W 0 to 500 0.1 [%]
123Eh
V/F characteristic curve
selection, 1st motor
A044 R/W
0 (VC), 1 (VP), 2 (free V/f), 3 (sensorless
vector control),
-
123Fh V/f gain A045 R/W 20 to 100 1 [%]
1240h
Voltage compensation gain
setting for automatic torque
boost, 1st motor
A046 R/W 0 to 255 1 [%]
1241h
Slippage compensation gain
setting for automatic torque
boost, 1st motor
A047 R/W 0 to 255 1 [%]
1242h
to1244h
(Reserved) - - - -
1245h DC braking enable A051 R/W
0 (disabling), 1 (enabling), 2 (output freq <
[A052])
-
1246h DC braking frequency A052 R/W 0 to 6000 0.01 [Hz]
1247h DC braking wait time A053 R/W 0 to 50 0.1 [sec.]
1248h
DC braking force during
deceleration
A054 R/W 0 to 100 1 [%]
1249h
DC braking time for
deceleration
A055 R/W 0 to 600 0.1 [sec.]
124Ah
DC braking/edge or level
detection for [DB] input
A056 R/W 0 (edge operation), 1 (level operation) -
124Bh DC braking force for starting A057 R/W 0 to 100 1 [%]
124Ch DC braking time for starting A058 R/W 0 to 600 0.1 [sec.]
124Dh
DC braking carrier frequency
setting
A059 R/W 20 to 150 0.1 [kHz]
124Eh (Reserved) - - - -