B−33
Register
No.
Function name Function code R/W Monitoring and setting items
Data
resolution
124Fh
Frequency upper limit
A061 (high) R/W
0 or "maximum frequency limit" to
"maximum frequency"
0.01 [Hz]
1250h A061 (low) R/W
1251h
Frequency lower limit
A062 (high) R/W
0 or "maximum frequency limit" to
"maximum frequency"
0.01 [Hz]
1252h A062 (low) R/W
1253h
Jump freq. (center) 1
A063 (high) R/W
0 to 40000(100000) 0.01 [Hz]
1254h A063 (low) R/W
1255h
Jump freq. width
(hysteresis) 1
A064 R/W 0 to 1000(10000) 0.01 [Hz]
1256h
Jump freq. (center) 2
A065 (high) R/W
0 to 40000(100000) 0.01 [Hz]
1257h A065 (low) R/W
1258h
Jump freq. width
(hysteresis) 2
A066 R/W 0 to 1000(10000) 0.01 [Hz]
1259h
Jump freq. (center) 3
A067 (high) R/W
0 to 40000(100000) 0.01 [Hz]
125Ah A067 (low) R/W
125Bh
Jump freq. width
(hysteresis) 3
A068 R/W 0 to 1000(10000) 0.01 [Hz]
125Ch
Acceleration hold frequency
A069 (high) R/W
0 to 40000 0.01 [Hz]
125Dh A069 (low) R/W
125Eh Acceleration hold time A070 R/W 0 to 600 0.1 [sec.]
125Fh PID Function Enable A071 R/W
0 (disabling), 1 (enabling), 2 (enabling
inverted-data output)
-
1260h PID proportional gain A072 R/W 0 to 2500 0.10
1261h PID integral time constant A073 R/W 0 to 36000 0.1 [sec.]
1262h PID derivative gain A074 R/W 0 to 10000 0.01 [sec.]
1263h PV scale conversion A075 R/W 1 to 9999 0.01
1264h PV source A076 R/W
0 (input via OI), 1 (input via O), 2 (external
communication), 3 (pulse train frequency
input), 10 (operation result output)
-
1265h Reverse PID A077 R/W 00 (disabling), 01 (enabling) -
1266h PID output limite
A078 R/W 0 to 1000 0.1 [%]
1267h PID feed forward selection A079 R/W 0 (disabled), 1(O input), 2 (OI input) -
1268h (Reserved) - R/W - -
1269h AVR function select A081 R/W
0 (always on), 1 (always off), 2 (off during
deceleration)
-
126Ah AVR voltage select A082 R/W
200 V class: 0 (200)/1 (215)/2 (220)/3
(230)/4 (240)
400 V class: 5 (380)/6 (400)/7 (415)/8
(440)/9 (460)/ 10 (480)
-
126Bh AVR filter time constant A083
R/W
0.000 to 10.00 0.001[sec]
126Ch AVR deceleration gain A084
R/W
50 to 200 1[%]
126Dh
Energy-saving operation
mode
A085 R/W
0 (normal operation), 1 (energy-saving
operation)
-
126Eh Energy-saving mode tuning A086 R/W 0 to 1000 0.1 [%]