In standard operation, the inverter uses a reference source selected by parameter A001
for the output frequency, which may be a fixed value (F001), a variable set by the front
panel potentiometer, or value from an analog input (voltage or current). To enable PID
operation, set A071=01. This causes the inverter to calculate
the target freq, or setpoint.
A calculated target frequency can have a lot of advantages. It lets the inverter adjust
the motor speed to optimize some other process of interest, potentially saving energy as
well. Refer to the figure below. The motor acts upon the external process. To control that
external process, the inverter must monitor the process variable. This requires wiring a
sensor to either the analog input terminal [O] (voltage) or terminal [OI] (current).
When enabled, the PID loop calculates the ideal output frequency to minimize the loop
error. This means we no longer command the inverter to run at a particular frequency,
but we specify the ideal value for the process variable. That ideal value is called the
setpoint, and is specified in the units of the external process variable. For a pump
application it may be gallons/minute, or it could be air velocity or temperature for an
HVAC unit. Parameter A075 is a scale factor that relates the external process variable
units to motor frequency. The figure below is a more detailed diagram of the function.
Setpoint
SP
+
PID
Calculation
Error Freq.
Inverter Motor
External
Process
Sensor
Process Variable (PV)
PV
Standard setting
F001
Multi-speed
setting
A020 A035
to
POT meter on
ext. panel
A075
1
Setpoint
(Target)
Scale factor
Reciprocal
A001
Frequency
source select
+
A072
P gain
A073
I gain
A074
D gain
+
Frequency
setting
A075
Scale factor
F001
SP
A101
A102
A105
A103
A104
V/I select
[AT]
[L]
A
GND
[O]
Voltage
[OI]
Current
A076
PID V/I input select
Process variable (Feedback)
A
nalog input scaling (OI)
d004 A075
Scale factor Monitor