363
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
B040
Torque limit selection Four option codes:
00Quadrant-specific setting
mode
01Terminal-switching mode
02Analog voltage input mode(O)
U
00
B041
Torque limit 1 (fwd/power) Torque limit level in forward
powering quadrant, range is 0 to
200%/no(disabled)
U
200 %
B022
Overload restriction level Sets the level of overload
restriction, between 20% and
200% of the rated current of the
inverter, setting resolution is 1% of
rated current
U
Rated
current
x 1.5
Amps
B043
Torque limit 3 (rev/power) Torque limit level in reverse
powering quadrant, range is 0 to
200%/no(disabled)
U
200 %
B044
Torque limit 4 (fwd/regen.) Torque limit level in forward
regen. quadrant, range is 0 to
200%/no(disabled)
U
200 %
b045
Torque LAD STOP
selection
Two option codes:
00Disable
01Enable
U
00
When “00” is specified for the torque
limit selection (b040), the torque limits 1
to 4 apply as shown to the top right.
When “00” is specified for the torque
limit selection (b040), the torque limit 1
to 4 are set as shown to the bottom right.
The torque limit 1 to 4 are switched by
the torque limit switches 1 and 2
assigned to intelligent input terminals 7
and 8, respectively for example:
When applying the torque limit function
to the motor operation at low speed, also
use the overload restriction function to
get more stable performance.
Related parameters: Over torque / under torque signal
Forward rotation
Reverse rotation
Regeneration
(
b042)
Torque
(+)
Torque
(-)
Powering
(
b043)
Powering
(
b041)
Regeneration
(
b044)
41 42
CM1
7 6
OFF OFF b041
ON OFF b042
OFF ON b043
ON ON b044