3−71
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
B092
Cooling fan control Selects when the fan is ON during
inverter operation, four options:
00…Fan is always ON
01…Fan is ON during run, OFF
during stop (5 minute delay
from ON to OFF)
02…Fan is temperature controlled
U
01
−
B093
Clear elapsed time of
cooling fan
Two option codes:
00…Count
01…Clear
U
00
−
b094
Initialization target data Select initialized parameters, four
option codes:
00…All parameters
01…All parameters except
in/output terminals and
communication.
02…Only registered parameters in
Uxxx.
03…All parameters except
registered parameters in Uxxx
and b037.
U
00
−
b095
Dynamic braking control
(BRD) selection
Three option codes:
00…Disable
01…Enable during run only
02…Enable always
U
01
−
b096
BRD activation level Range is:
330 to 380V (200V class)
660 to 760V (400V class)
U
360/
720
V
b180
Initialization trigger
(*)
This is to perform initialization by
parameter input with b084, b085
and b094. Two option codes:
00…Initialization disable
01…Perform initialization
U
00
−
(*) Note: When 01 is set on b180, and SET key is pressed, initialization starts
immediately and there is not any way to restore the previous parameter setting. WJ200
doesn’t have a method to trigger the initialization by key action as the other Hitachi
inverter models have.