434
It is possible for the inverter to retain the frequency set from the [UP] and [DWN]
terminals through a power loss. Parameter C101 enables/disables the memory. If
disabled, the inverter retains the last frequency before an UP/DWN adjustment. Use
the [UDC] terminal to clear the memory and return to the original set output
frequency.
Option
Code
Terminal
Symbol
Function Name State Description
27
UP Remote Control UP
Function (motorized
speed pot.)
ON Accelerates (increases output frequency) motor
from current frequency
OFF Output to motor operates normally
28
DWN Remote Control
DOWN Function
(motorized speed
pot.)
ON Decelerates (increases output frequency) motor
from current frequency
OFF Output to motor operates normally
29
UDC Remote Control Data
Clear
ON Clears the Up/Down frequency memory
OFF No effect on Up/Down memory
Valid for inputs:
C001~C007
Example (default input configuration shown—see
page 3–84):
See I/O specs on page 4–6.
Required settings
A001 = 02
Notes:
This feature is available only when the frequency
command source is programmed for operator
control. Confirm A001 is set to 02.
This function is not available when [JG] is in use.
The range of output frequency is 0 Hz to the value
in A004 (maximum frequency setting).
This setting modifies the inverter speed from using F001 output frequency setting as a starting point.
DWN UP
7654321L
PCS
P24
PLC