C−4
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
A014
[O] input active range end
voltage
The ending point (offset) for the
active analog input range,
range is 0. to 100.
U
100. %
A015
[O] input start frequency
enable
Two options; select codes:
00…Use offset (A011 value)
01…Use 0Hz
U
01
−
A016
Analog input filter Range n = 1 to 31,
1 to 30 : ×2ms filter
31: 500ms fixed filter with ±
0.1kHz hys.
U
8. Spl.
A017
9
00 -
a019
Multi-speed operation
selection
Select codes:
00...Binary operation (16 speeds
selectable with 4 terminals)
01...Bit operation (8 speeds
selectable with 7
terminals)
U
00 -
A020
Multi-speed freq. 0 Defines the first speed of a
multi-speed profile, range is 0.0
/ start frequency to 400Hz
A020 = Speed 0 (1st motor)
9
0.0 Hz
A220
Multi-speed freq. 0,
2
nd
motor
Defines the first speed of a
multi-speed profile or a 2nd
motor, range is 0.0 / start
frequency to 400Hz
A220 = Speed 0 (2nd motor)
9
0.0 Hz
A021
to
A035
Multi-speed freq. 1 to 15
(for both motors)
Defines 15 more speeds,
range is 0.0 / start frequency to
400 Hz.
A021=Speed 1 ~ A035=Speed15
9
See next
row
Hz
A021 ~ A035
9
0.0 Hz
A038
Jog frequency Defines limited speed for jog,
range is from start frequency to
9.99 Hz
9
6.00 Hz
A039
Jog stop mode Define how end of jog stops the
motor; six options:
00…Free-run stop (invalid
during run)
01…Controlled deceleration
(invalid during run)
02…DC braking to stop(invalid
during run)
03…Free-run stop (valid during
run)
04…Controlled deceleration
(valid during run)
05…DC braking to stop(valid
during run)
U
04
−
A041
Torque boost select Two options:
00…Manual torque boost
U
00
−