C−12
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
b011
Retry wait time on over
voltage / over current trip
Range is 0.3 to 100 sec.
U
1.0 sec
B012
Level of electronic thermal Set a level between 20% and 100%
for the rated inverter current.
U
Rated
current for
each
inverter
model *1
A
B212
Level of electronic thermal,
2
nd
motor
U
A
B013
Electronic thermal
characteristic
Select from three curves, option
codes:
00…Reduced torque
01…Constant torque
02…Free setting
U
01
−
B213
Electronic thermal
characteristic, 2
nd
motor
U
01
−
b015
Free setting electronic
thermal ~freq.1
Range is 0 to 400Hz
U
0.0 Hz
b016
Free setting electronic
thermal ~current1
Range is 0 to inverter rated
current Amps
U
0.00
Amps
b017
Free setting electronic
thermal ~freq.2
Range is 0 to 400Hz
U
0.0 Hz
b018
Free setting electronic
thermal ~current2
Range is 0 to inverter rated
current Amps
U
0.00
Amps
b019
Free setting electronic
thermal ~freq.3
Range is 0 to 400Hz
U
0.0 Hz
b020
Free setting electronic
thermal ~current3
Range is 0 to inverter rated
current Amps
U
0.00
Amps
B021
Overload restriction
operation mode
Select the operation mode during
overload conditions, four options,
option codes:
00…Disabled
01…Enabled for acceleration and
constant speed
02…Enabled for constant speed
only
03…Enabled for acceleration and
constant speed, increase speed
at regen.
U
01
−
B221
Overload restriction
operation mode, 2
nd
motor
U
01
−
B022
Overload restriction level Sets the level of overload
restriction, between 20% and 200%
of the rated current of the inverter,
setting resolution is 1% of rated
current
U
Rated
current
x 1.5
Amps
B222
Overload restriction level,
2
nd
motor
U
Rated
current
x 1.5
Amps
B023
Deceleration rate at overload
restriction
Sets the deceleration rate when
inverter detects overload, range is
0.1 to 3000.0, resolution 0.1
U
1.0 sec.
B223
Deceleration rate at overload
restriction, 2
nd
motor
U
1.0 sec.