Model IFP-2000/ECS Installation Manual 151430-L8
8-23
System
Options
Auto Time Test
Set the Hour
*02:00AM Section 9.6.1Set the Minutes
Select AM/PM
Phone Lines Select Phone Line
For each phone line (1 & 2) select:
Dialing Prefix Up to 9 digits *none Section 9.6.1
# of Answer Rings Range: 00-15 *06
Number of
rings before
panel answers
a call from a
computer
Section
9.6.2.2
Select Dialing Option
TT
*TT
Touch Tone
TT/PL
TouchTone
alternating
with pulse see
Section
9.6.2.3
PULSE Pulse dialing
Rotary Pulse Format
U = 60/40
*U
Section
9.6.2.4
E = 66/34
Dial Tone Disabled Y or N *N
Monitor Line Y or N *N
Section
9.6.2.6
Answering Machine
Bypass
Y or N *N
Section
9.6.2.7
Phone Line Unused Y or N *N
Section
Figure 9.6.2.8
on page 22
Daytime/Nighttime
Sensitivity
Enable/Disable
Yes
*No
Section 9.6.3
No
Day Start Enter time *6:00AM
Night Start Enter time *6:00PM
Days of the Week Select days *-MTWTF-
Holiday Days Holidays 1 to 18 Enter dates
*01/01, 07/
04, 12/24,
12/25
Section 9.6.4
Time Options
Water Flow Delay 0 - 90 Seconds *1 sec
Water Flow delay is the
number of seconds before a
water flow alarm is
generated. Section 9.6.5.1
Alarm Verification Time 1 to 250 seconds *60 sec
Alarm Verification time
section 9.6.5.2
Low AC Report Time 0 - 30 hours *3 hrs
Low AC Report Delay.
Section 9.6.5.3
Menu Options/Defaults Comments

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt IFP-2000 and is the answer not in the manual?

Honeywell Farenhyt IFP-2000 Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt IFP-2000
CategoryConference System
LanguageEnglish

Related product manuals