Model IFP-2000/ECS Installation Manual 151430-L8
3-17
Mount the control panel cabinet.
4.1
Connect AC.
4.2
Connect phone lines.
4.11
Install 5815XL SLC expander modules.
4.6
Install RA-2000 Remote Fire Alarm Annunciator modules.
4.5
Install 5865 or LED Annunciator modules.
4.9
Install 5880 LED I/O modules.
4.8
Install notification appliances.
4.12.1
Install auxiliary power devices.
4.12.5
Install 5824 Serial/Parallel Printer Interface Module.
4.7
Connect batteries (typically last step).
4.3
SLC Device Hardware Installation Perform these steps before running JumpStart AutoProgramming.
Connect device bases to the loop.
IDP 7.5
SD 7.7
Set device addresses.
IDP 7.6
SD 7.8
Physically connect detectors to their bases. Connect relay and contact monitor
modules.
7.4 & see device
install instructions
JumpStart AutoProgramming
JumpStart AutoProgramming searches for expanders and SLC devices connected to the panel but
not programmed into the system. JumpStart AutoProgramming automatically selects some options
for SLC devices. See “Input Point (SLC Device) Configuration” section of this chart for other options.
JumpStart AutoProgramming makes selections for the following options. You can customize options,
if necessary.
8.2 & 9.7
Device type (detector or switch) configured by JumpStart AutoProgramming. To change, see 9.7
Program type of detector (heat, photoelectric, or ionization) selected by JumpStart
AutoProgramming.
To change, see 9.7
System Software Configuration
Select low AC hours report time (3 hours by default).
9.6.5.3
Enable/disable automatic DST adjustment feature (enabled by default).
9.6.7.1
Change clock display format (12-hour with AM/PM by default).
9.6.5.5
Enable/disable day/night sensitivity (disabled by default).
9.6.3
Select holiday schedule (up to 18 days) if installation is using day/night sensitivity.
9.6.4
Select options for phone lines.
9.6.2
Customize banner message (message that displays on LCD in normal mode) if
desired.
9.6.8
Input Point (SLC Device) Configuration
JumpStart AutoProgramming automatically selects some options for SLC devices (see “JumpStart AutoProgramming”
section of this chart). You can change options selected by JumpStart AutoProgramming, if necessary and further customize
input point options.
Select device family (IDP or SD). Only one device family can be used per control
panel.
9.6.9
Task
See Section
(for more info.)