5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 125
July 2010 Honeywell
Step Action Result
TIP
If your system will include multiple FIMs, we suggest that you adopt a more structured
syntax for naming them. For example, use the MAC ID for the Supervisory ControlNet
module and the CIOM-A FIM's slot location in the chassis to form a meaningful suffix.
For the CIOM-A FIM used in this procedure, the suggested name would be FIM0105.
2
Key in >FIM0105< for this example.
Press <Tab>.
Note that Control Builder automatically
assigns a name with a unique suffix. You
can enter a name of your choice
consisting of up to 16 characters. The
only rule is that it must be unique within
the system.
Moves cursor to the Network Name field
and highlights it.
3
Be sure the communications medium
your Experion system is using appears in
the Network Name field. If it doesn't, use
the field's dropdown list to select it.
ControlNet is the default selection. Press
<Tab>.
Moves cursor to the Driver Name field
and highlights it.
TIP
Communications Driver must be installed and running before it will appear as a
selection in the dropdown menu for this field.