5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
128 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action Result
10
Click
button to select slot number
where downlink ControlNet Module is
installed from dropdown list. Use slot 04
for this example. Press <Tab>.
(Remember that chassis slot numbering
is zero-based from left to right.)
Moves cursor to UpLink MAC Address
field.
11
Click
button to select address of the
ControlNet Network module in the
Remote I/O chassis that is connected to
the ControlNet Network module
(Downlink) in the Supervisory Chassis.
Use 05 for this example. Press <Tab>.
Moves cursor to UpLink Slot Number
field.