5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 129
July 2010 Honeywell
Step Action Result
12
Click
button to select slot number
where uplink ControlNet Module is
installed from dropdown list. Use slot 00
for this example. Press <Tab> twice.
(Remember that chassis slot numbering
is zero-based from left to right.)
Moves cursor to This controller is
redundant field.
13
Click check box to add check mark, if this
CIOM-A FIM is part of a Redundant
Chassis Pair. Leave check box blank, if
CIOM-A FIM is part of a non-redundant
chassis configuration. Press <Tab>.
If box is checked, default name for
seconday CIOM-A FIM appears in
Secondary Name field. Go to Next
Step.
If box is blank, moves cursor to
Item Name field. Go to Step 15.
14
Only valid when CIOM-A FIM is
redundant. Key in desired name for
secondary CIOM-A FIM or accept default
that is assigned name with SEC
appended. Press <Tab>.
See second bullet in row above.
15
Key in the name of the Entity that this
object will be associated with in the
Enterprise Model Builder hierarchy.
Press <Tab>.
Moves cursor to the FIM Command field.