5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
160 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action Result
8
Press <Tab>.
Moves cursor to the Step Timer Preset
(T1) field and highlights it.
9
Accept default value for Step Time
Preset (T1) parameter or key in a new
value. This is the preset value for the
System Management step timer. The
default value is 15. 0000s. Press <Tab>.
Moves cursor to the Preset Set Addr Seq
Timer (T2) field and highlights it.
10
Accept the default value for the Preset
Set Addr Seq Timer (T2) parameter or
key in a new value. This is the preset
value for the System Management set
address sequence timer. The default
value is 01:30. 0000s. Press <Tab>.
Moves cursor to the Preset Set Addr Wait
Timer (T3) field and highlights it.
11
Accept the default value for the Preset
Set Addr Wait Timer (T3) parameter or
key in a new value. This is the preset
value for the SM set address wait timer.
The default value is 45. 0000s. Click the
Network Management (LM) tab.
Calls up the Network Management (LM)
tab.
ATTENTION
The remaining parameters on the System Management tab and the Network
Management (Basic) tab are read only and provided for monitoring purposes only.