5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 199
July 2010 Honeywell
Step Action Result
1
With CM102 chart open, click the
parameter connector button in the
toolbar.
Cursor shape changes to cross-hairs
.
2
Click SI pin on DEVCTL block. Double-
click area adjacent to pin.
Parameter connection box appears.
3
Click button .
Opens the Point Selector dialog box.
4
Scroll in the Point Names list box to find
CM101 DATAACQ_101. Click point.
Populates the Parameters list box with
applicable parameters related to the
point.