5. Configuration
5.4. Configuring Fieldbus Components In a Control Strategy
200 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action Result
5
Scroll in the Parameters list box to find
parameter PVLLALM.FL. Click
PVLLALM.FL.
Parameter is inserted into the parameter
Selected Item field.
6
Click the Select button.
Parameter name is inserted into the
parameter connection box.
7
Click IN pin on FTRIGA block. Double-
click area adjacent to pin.
Parameter connection box appears.
8
Repeat Steps 3 to 6 to select parameter
CM101.DATAACQ_101.PVLOALM.FL
for this connection box.
See the following figure for a completed
CM102 with parameter connections.
9
Close Point Selector dialog box. This
completes the addition of parameter
connections for sample loop interlocks
and the CM creation tutorial. Go to the
next section Loading Components
Online.