8. Maintenance, Checkout, and Calibration
8.7. Using Fieldbus Device Simulate Function
R400 Experion PKS Series A Fieldbus Interface Module User's Guide 339
July 2010 Honeywell
Step Action Result
7
Click Yes.
Initiates the simulate function. Check that
the Simulation Active button is ON in the
Block Errors (Blk Alarm) list on the form.
8
Click the button in the Simulate
Status field.
Opens drop-down menu.
9
For this example, select Good from the
menu.
Opens Change Online Value
confirmation dialog.
10
Click Yes. Sets Simulate Status to Good.
11
Press <Tab>. Moves cursor to the Simulate Value field.