8. Maintenance, Checkout, and Calibration
8.7. Using Fieldbus Device Simulate Function
340 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
Step Action Result
12
Key in >25< and press <Enter>.
Opens Change Online Value
confirmation dialog.
13
Click Yes. Sets Simulate Value to 25.
ATTENTION
With R400, the parameter Enable Block Offnet Diagnostic Alarm appears on the
Maintenance tab of Resource blocks, Transducer blocks, and other function blocks
that support block errors. By default, this parameter is disabled, which means that the
Block Offnet Alarm is not reported if a device that contains the block goes off the
network.
Before configuring the Enable Block Offnet Diagnostic Alarm parameter, consider the
following conditions:
If you enable the Enable Block Offnet Diagnostic Alarm, the Block Offnet Alarm is
reported while the device, which contains the block, goes offnet.
If you disable the option while the alarm is active, the alarm returns to normal.
Therefore, you can configure this alarm before loading and it can be changed at
runtime while the device is offline. You can silence the alarm and prevent the
report generation.
14
Click the OK button. Closes the Block Parameters form.