3. Fieldbus Integration With Experion System
3.8. Block Instantiation Support
94 Experion PKS Series A Fieldbus Interface Module User's Guide R400
Honeywell July 2010
If you want
to . . .
Then, Notes and References
Load
Project
device to
physical
device.
m) See Load order guidelines
for
reference.
n) See Loading a FIM and its Links
for reference.
o) See Matching uncommissioned
device to project device or vice
versa for reference.
p) Right-click device icon and select
Load from short cut menu.
q) Review information on Load
dialog for load details and any
warning messages identifying pre-
load considerations.
r) Click OK button to initiate the load
and monitor Load Progress dialog
for load related activities.
s) Upon successful device load,
open device icon in Monitor tab to
view block hierarchy. Only
transducer and resource blocks
appear in the device hierarchy
after an initial load.
t) Right-click device icon and select
Upload from the shortcut menu.
Click Continue to load device data
into the Monitor database.
The existing load order,
FIM/Link load, and device
match functions also apply
for devices with instantiable
blocks.
Device load from Project
synchronizes the contents of
the project device with the
physical device and
instantiates applicable
instantiable blocks in the
physical device.
See About Load Dialog box
for general information.
See Loading Link contents
or fieldbus device for general
device load procedure.
You must load the Control
Module(s) containing fixed
and/or instantiated blocks
associated with the device
for the fixed and instantiated
blocks to appear in the
device hierarchy in
Monitoring tab.
After loading a device from
Project or Monitor tab, the
physical device function
block contents matches that
of the corresponding Project
or Monitor device. This
means necessary blocks will
be instantiated and
unnecessary Blocks will be
removed or de-instantiated.
A physical device may go offline while its instantiable blocks are
being instantiated through a device load.

Table of Contents