Paramete
r
Description Conguration
Principle
Default Value
L1/L2
linkage
fastest
temp rise
Maximum
temperature rise rate
when the temperature
rises rapidly caused by
sudden load power
increase.
Set this parameter
based on the micro-
module size and
maximum load power.
The smaller the
module and the
higher the load
power, the greater the
temperature rise rate
is.
4.0°C/min
L1/L2
linkage
temperatu
re
Temperature setpoint
in L1/L2 linkage.
Target temperature
controlled in the
micro-module. The
parameter can only
be modied on the
ECC WebUI and
cannot be
modied
on the smart cooling
product screen.
24.0°C
L1/L2
linkage
humidity
Humidity setpoint in
L1/L2 linkage.
Target humidity
controlled in the
micro-module. The
parameter can only
be modied on the
ECC WebUI and
cannot be
modied
on the smart cooling
product screen.
45.0%RH
Step 3 Complete the teamwork settings for all the smart cooling products by performing
Step 1 and Step 2.
Step 4 On the home screen of any teamwork controlled smart cooling product, tap
. If
the teamwork control succeeds, the teamwork topology of the smart cooling
product in the group is displayed, as shown in Figure 4-9. Table 4-8 describes the
note for the screen.