7. Maintenance and Inspection
7.1 Periodic Inspection
7-3 ME0342-4B
No.
Inspection
items
Inspection details
Judgment
criteria
Countermeasures
4
Connection
status
Wiring connectors
loose? (Motor encoder
cable, field network
cable, stop circuit and
absolute battery, etc.)
No looseness
Insert until the lock engages.
Wiring cable frayed?
No visual
abnormalities
Check visually and replace the cable.
5
Absolute
battery
Absolute battery (AB-
7)
beyond expiry date or
lifespan?
The expiry date is
3 years and
should not
exceed the date
written on a
sticker adhered
to the battery
body
Even if the absolute battery is free of
errors, replace it if the expiry date has
passed.
Refer to [7.4.1 How to Replace
Absolute Battery] for how to make
replacement.
6
Preventive/
predictive
maintenance
function
Preventive/predictive
maintenance alarms
generated?
No alarm
generated
Refer to [7.5 Preventive Maintenance
Function] and [7.6 Predictive
Maintenance Function] for
countermeasures.

Table of Contents

Other manuals for IAI PCON-CB series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IAI PCON-CB series and is the answer not in the manual?

IAI PCON-CB series Specifications

General IconGeneral
BrandIAI
ModelPCON-CB series
CategoryController
LanguageEnglish

Related product manuals