What to do if INVT SV-DA200 show main circuit undervoltage fault?
- OOlivia DavisAug 31, 2025
If your INVT Servo Drive displays a main circuit undervoltage fault, it means the detected DC voltage of the drive's main circuit is lower than the specified voltage. To troubleshoot: 1. Make sure the grid input voltage is within the allowed range. 2. Re-power on and ensure the buffer relay is closed (you should hear a sound indicating actuation). 3. Check parameter R0.07 when the drive is disabled; if it's abnormal and doesn't match the grid input voltage, replace the drive.