Address Name Default seng Category Data type Factor A M
0x2633:002 Digital input debounce me: Digital input 2 1 ms general U8 1 P -
0x2633:003 Digital input debounce me: Digital input 3 1 ms general U8 1 P -
0x2633:004 Digital input debounce me: Digital input 4 1 ms general U8 1 P -
0x2633:005 Digital input debounce me: Digital input 5 1 ms general U8 1 P -
0x2634:001
(P420.01)
Digital outputs funcon: Relay Ready for
operaon [51] general U8 1 P -
0x2634:002
(P420.02)
Digital outputs funcon: Digital output 1 Release holding brake
[115]
general U8 1 P -
0x2635:001
(P421.01)
Inversion of digital outputs: Relay Not inverted [0] general U8 1 P -
0x2635:002
(P421.02)
Inversion of digital outputs: Digital output 1 Not inverted [0] general U8 1 P -
0x2636:001
(P430.01)
Analog input 1: Input range 0 ... 10 VDC [0] general U8 1 P -
0x2636:002
(P430.02)
Analog input 1: Min frequency value 0.0 Hz general I16 10 P -
0x2636:003
(P430.03)
Analog input 1: Max frequency value Device for 50-Hz mains:
50.0 Hz Device for 60-Hz
mains: 60.0 Hz
general I16 10 P -
0x2636:004
(P430.04)
Analog input 1: Min PID value 0.00 PID unit general I16 100 P -
0x2636:005
(P430.05)
Analog input 1: Max PID value 100.00 PID unit general I16 100 P -
0x2636:006
(P430.06)
Analog input 1: Filter me 10 ms general U16 1 P -
0x2636:007
(P430.07)
Analog input 1: Dead band 0.0 % general U16 10 P -
0x2636:008
(P430.08)
Analog input 1: Monitoring threshold 0.0 % general I16 10 P -
0x2636:009
(P430.09)
Analog input 1: Monitoring condion Input value < trigger
thr
eshold [0]
general U8 1 P -
0x2636:010
(P430.10)
Analog input 1: Error response Fault [3] general U8 1 P -
0x2636:011
(P430.11)
Analog input 1: Min torque value 0.0 % general I16 10 P -
0x2636:012
(P430.12)
Analog input 1: Max torque value 100.0 % general I16 10 P -
0x2637:001
(P431.01)
Analog input 2: Input range 0 ... 10 VDC [0] general U8 1 P -
0x2637:002
(P431.02)
Analog input 2: Min frequency value 0.0 Hz general I16 10 P -
0x2637:003
(P431.03)
Analog input 2: Max frequency value Device for 50-Hz mains:
50.0 Hz Device for 60-Hz
mains: 60.0 Hz
general I16 10 P -
0x2637:004
(P431.04)
Analog input 2: Min PID value 0.00 PID unit general I16 100 P -
0x2637:005
(P431.05)
Analog input 2: Max PID value 100.00 PID unit general I16 100 P -
0x2637:006
(P431.06)
Analog input 2: Filter me 10 ms general U16 1 P -
0x2637:007
(P431.07)
Analog input 2: Dead band 0.0 % general U16 10 P -
0x2637:008
(P431.08)
Analog input 2: Monitoring threshold 0.0 % general I16 10 P -
0x2637:009
(P431.09)
Analog input 2: Monitoring condion Input value < trigger
thr
eshold [0]
general U8 1 P -
0x2637:010
(P431.10)
Analog input 2: Error response Fault [3] general U8 1 P -
* Default seng dependent on the model.
Appendix
P
arameter aribute list
318