EasyManua.ls Logo

Lenze i410 - Page 326

Lenze i410
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Address Name Default seng Category Data type Factor A M
0x2DA5:016
(P111.16)
Diagnoscs of analog input 2: Status - (Read only) general U16 1 O -
0x2DAA:001
(P112.01)
Diagnoscs of analog output 1: Voltage x.xx V (Read only) general U16 100 O t
0x2DAA:002
(P112.02)
Diagnoscs of analog output 1: Current x.xx mA (Read only) general U16 100 O t
0x2DAC
(P119.00)
Keypad status - (Read only) general U16 1 O t
0x2DAD
(P120.00)
Internal hardware states - (Read only) general U16 1 O -
0x2DAE:001
(P140.01)
Sequencer
diagnoscs: Acve step - (Read only) Sequencer U8 1 O t
0x2DAE:002
(P140.02)
Sequencer diagnoscs: Step me elapsed x.x s (Read only) Sequencer I32 10 O t
0x2DAE:003
(P140.03)
Sequencer diagnoscs: Step me remaining x.x s (Read only) Sequencer I32 10 O t
0x2DAE:004
(P140.04)
Sequencer diagnoscs: Steps complete - (Read only) Sequencer I32 1 O t
0x2DAE:005
(P140.05)
Sequencer diagnoscs: Steps remaining - (Read only) Sequencer I32 1 O t
0x2DAE:006
(P140.06)
Sequencer diagnoscs: Acve sequence - (Read only) Sequencer U8 1 O t
0x2DAE:007
(P140.07)
Sequencer diagnoscs: Acve segment - (Read only) Sequencer U8 1 O t
0x2DAE:008
(P140.08)
Sequencer
diagnoscs: Relave sequence me
remaining
x % (Read only) Sequencer U8 1 O t
0x2DAE:009
(P140.09)
Sequencer diagnoscs: Absolute sequence me
remaining
x.x s (Read only) Sequencer I32 10 O t
0x2DAE:010 Sequencer diagnoscs: Frequency setpoint x.x Hz (Read only) Sequencer I16 10 - -
0x2DAE:011 Sequencer diagnoscs: PID setpoint x.xx PID unit (Read only) Sequencer I16 100 - -
0x2DAE:012 Sequencer diagnoscs: Torque setpoint x.x % (Read only) Sequencer I16 10 - -
0x2DD1:001 Motor currents: Actual D-current (id) x.xx A (Read only) MCTRL I32 100 O t
0x2DD1:002 Motor currents: Actual Q-current (iq) x.xx A (Read only) general I32 100 O t
0x2DD1:003 Motor currents: Setpoint D-current (id) x.xx A (Read only) general I32 100 O t
0x2DD1:004 Motor currents: Setpoint Q-current (iq) x.xx A (Read only) MCTRL I32 100 O t
0x2DD1:005 Motor currents: Motor current (Ie) x.xx A (Read only) MCTRL I32 100 O t
0x2DD3:003 Speed setpoint limited x rpm (Read only) MCTRL I32 1 O t
0x2DD5 Torque setpoint x.xx Nm (Read only) general I32 100 - t
0x2DDD
(P100.00)
Output frequency x.x Hz (Read only) general I16 10 O t
0x2DDF:001 Axis
informaon: Rated current x.xx A (Read only) general U16 100 O t
0x2DDF:002 Axis informaon: Maximum current x.xx A (Read only) general U16 100 O t
0x2DE0:009 Motor idencaon sengs 0 general U16 1 PC -
0x2DE0:010 V/f behavior 0 general U16 1 PC -
0x4002
(P702.00)
Speed display scaling 0.00 general U16 100 P -
0x4003
(P413.00)
MOP starng mode Last value [0] general U8 1 P -
0x4004:001
(P414.01)
MOP
starng values: Frequency 0.0 Hz general U16 10 P -
0x4004:002
(P414.02)
MOP starng values: PID value 0.00 PID unit general I16 100 P -
0x4004:003
(P414.03)
MOP starng values: Torque 0.0 % general U16 10 P -
0x4005
(P412.00)
Frequency threshold 0.0 Hz general U16 10 P -
0x4006:001
(P710.01)
Load loss detecon: Threshold 0.0 % general U16 10 P -
* Default seng dependent on the model.