Address Name Default seng Category Data type Factor A M
0x4006:002
(P710.02)
Load loss detecon: Delay
me 0.0 s general U16 10 P -
0x4006:003
(P710.03)
Load loss detecon: Error response No response [0] general U8 1 P -
0x4007:001 Heavy load monitoring: Error threshold 200.0 % general U16 10 P -
0x4007:002 Heavy load monitoring: Delay me 3.0 s general U16 10 P -
0x4007:003 Heavy load monitoring: Error response No response [0] general U8 1 P -
0x4009:001 MOP values saved: Frequency x.x Hz (Read only) general U16 10 - t
0x4009:002 MOP values saved: PID value x.xx PID unit (Read only) general I16 100 - t
0x4009:003 MOP values saved: Torque x.x % (Read only) general U16 10 - t
0x4009:004 MOP values saved: Frequency setpoint x.x Hz (Read only) general I16 10 - -
0x4009:005 MOP values saved: PID setpoint x.xx PID unit (Read only) general I16 100 - -
0x4009:006 MOP values saved: Torque setpoint x.x % (Read only) general I16 10 - -
0x400B:011
(P592.11)
PID feedback 0.00 PID unit general I16 100 OK r
0x400D
(P101.00)
Scaled actual value x Units (Read only) general I16 1 O t
0x4016:003 Digital output 1: Cutout delay 0.000 s general U16 1000 P -
0x4016:004 Digital output 1: Switch-on delay 0.000 s general U16 1000 P -
0x4016:005 Digital output 1: Terminal state - (Read only) general U8 1 - -
0x4016:006 Digital output 1: Trigger signal state - (Read only) general U8 1 - -
0x4018:003 Relay: Switch-o delay 0.000 s general U16 1000 P -
0x4018:004 Relay: Switch-on delay 0.000 s general U16 1000 P -
0x4018:005 Relay: Relay state - (Read only) general U8 1 - -
0x4018:006 Relay: Trigger signal state - (Read only) general U8 1 - -
0x4018:007 Relay: Switching cycles - (Read only) general U32 1 - -
0x401F:001
(P121.01)
Current setpoint x.xx PID unit (Read only) general I16 100 O t
0x401F:002
(P121.02)
Current process variable x.xx PID unit (Read only) general I16 100 O t
0x401F:003
(P121.03)
Status - (Read only) general U8 1 O t
0x401F:004 PID control value x.x Hz (Read only) general I16 10 - -
0x401F:005 PID Feedforward value x.x Hz (Read only) general I16 10 - -
0x401F:006 PID output value x.x Hz (Read only) general I16 10 - t
0x401F:007 PID error value x.xx PID unit (Read only) general I32 100 - -
0x4020:001
(P600.01)
Process controller setup (PID): Operang mode Inhibited [0] general U8 1 P -
0x4020:002
(P600.02)
Process controller setup (PID): PID process variable Analog input 1 [1] general U8 1 P -
0x4020:003
(P600.03)
Process controller setup (PID): Closed-loop
c
ontrolled speed range
100 % general U16 1 P rt
0x4020:004
(P600.04)
Process controller setup (PID): Speed feedforward
control source
Without speed addion
[0]
general U8 1 P -
0x4020:005
(P600.05)
Process controller setup (PID): Min speed limit -100.0 % general I16 10 P -
0x4020:006
(P600.06)
Process controller setup (PID): Max speed limit 100.0 % general I16 10 P -
0x4021:001
(P606.01)
PID speed operaon: Acceleraon me 1.0 s general U16 10 P -
0x4021:002
(P606.02)
PID speed
operaon: Deceleraon me 1.0 s general U16 10 P -
0x4022:001
(P451.01)
PID setpoint presets: Preset 1 0.00 PID unit general I16 100 P -
0x4022:002
(P451.02)
PID setpoint presets: Preset 2 0.00 PID unit general I16 100 P -
* Default seng dependent on the model.
Appendix
P
arameter aribute list
327